DC Wire Size Calculator
Size copper DC wire or cable for 12V, 24V and 48V systems. Enter amps and one-way length to check AWG, voltage drop and NEC ampacity.
The formula, every assumption, and the primary sources behind this tool are published on this page.
Results
Recommended copper wire: 6 AWG
Voltage drop is what sizes this cable.
One-way conductor length: 15 ft / 4.572 m
Geometric cross-sectional area: 13.3 mm²
mm² is converted from this AWG row's circular mils. It does not select a metric standard wire or establish its ampacity.
Circular mils the drop formula asks for: 21,500
Circular mils of the recommended gauge: 26,240
Voltage drop on the recommended gauge: 0.29 V (2.46%)
Voltage at the load: 11.71 V
Heat lost in the cable: 5.89 W
Ampacity the cable must cover: 20 A
Effective ampacity of the recommended gauge: 65 A
12V, 24V and 48V DC cable sizing examples
Each example carries 20 A over 15 ft one way, with a 3% voltage-drop limit and a non-continuous load. Results use the copper tables and assumptions below. Open an example to change the current, length or duty cycle.
| Voltage | Copper wire | Actual drop |
|---|---|---|
| 12 V | 6 AWG | 2.46% |
| 24 V | 8 AWG | 1.94% |
| 48 V | 12 AWG | 2.47% |
How it works
A DC cable has to clear two independent checks: voltage drop on the round-trip run, and the current the copper (and its breaker) can carry. The circular-mil formula finds the drop-limited size; the pick is the smallest AWG that also passes the NEC ampacity table.
required_cm = 2 × K × I × L / VDVD = system_voltage × (voltage_drop_pct / 100)actual_drop_v = 2 × L × (R / 1000) × Iampacity_need = I, or I × 1.25 if continuousrecommended = smallest AWG with cmil ≥ required_cm AND actual_drop_v ≤ VD AND effective_ampacity ≥ ampacity_need
K- 12.9 — IAEI copper k-factor at 75 °C, derived from NEC Chapter 9 Table 8 (ohm/kFT × circular mils).
I- DC current on the run, in amperes. DC-side watts divide by voltage; inverter AC watts divide by battery voltage × 0.90 (same as the inverter-size tool). Voltage drop uses this number even when the load is continuous.
L- One-way length in feet. Both formulas multiply by 2 for the return conductor.
VD- Allowed drop in volts: system voltage × (budget percent ÷ 100). At 12 V and 3% that is 0.36 V.
required_cm- Minimum circular mils from the k-factor formula. A gauge still has to beat this number.
actual_drop_v- Round-trip drop using that gauge's Table 8 stranded resistance at 75 °C, not the rounded k-factor.
ampacity_need- Current the conductor must be rated for. Continuous loads (3+ hours at a stretch) are multiplied by 1.25. 14/12/10 AWG then take the 240.4(D) cap of 15/20/30 A.
Assumptions
- 1 international foot = 0.3048 m exactly. Length is one-way; resistance includes the return. mm² is geometric area, not a separate metric conductor rating.
- Copper stranded cable only. Aluminum needs a different k-factor (about 21.2) and is not in v1.
- Length is one way. Entering a round-trip distance would double the drop a second time.
- Resistance is NEC Chapter 9 Table 8 at 75 °C, which matches 75 °C terminations (110.14(C)). Charts published at 20–30 °C (some marine tables) read about one size smaller.
- 14/12/10 AWG copper are capped at 15/20/30 A by NEC 240.4(D), even though Table 310.16 lists 20/25/35 A at 75 °C.
- 3% is the NEC 210.19 informational-note convention for a branch, not a mandatory Code rule. Feeder-plus-branch totaling 5% is the matching note.
- The 125% factor applies only to ampacity, and only when you mark the run continuous. Voltage drop stays on the amps you entered.
- A = W ÷ V is only correct for DC-side watts. Inverter AC output still has to cover inverter loss: A = W ÷ (V × 0.90), the same 90% default as the inverter-size tool. A 1,200 W inverter on 12 V is about 111 A on the DC cable, not 100 A.
- This tool sizes the conductor. It does not pick a fuse or breaker, place the OCPD, or apply ambient / bundling derates from 310.15.
- Boat and RV cable charts (ABYC E-11, some chassis-harness tables) are not the NEC table. They can recommend a different gauge for the same amps and feet.
FAQ
What size wire for 30 amps at 12 volts?
It depends on length. At the default 15 ft one-way and a 3% budget, 30 A on 12 V needs 4 AWG copper (6 AWG drops 3.7%). A 5 ft run of the same current is mostly an ampacity problem: 10 AWG would nearly hold 3%, but NEC 240.4(D) caps it at 30 A, so a continuous 30 A load still steps up.
Is 3% voltage drop a code requirement?
No. NEC 210.19's 3% / 5% figures sit in an informational note — they describe reasonable efficiency, they do not require a size. A 12 V inverter input is unforgiving of sag, so 3% is still the sensible default. Tighten it to 2% for electronics; loosen it only when you accept the extra heat.
Is wire length one-way or round trip?
One way — battery to the load. Both the circular-mil formula and the Table 8 resistance check multiply by 2 for the return conductor. If you type a round-trip tape measure, the drop is counted twice and the wire comes out a size (or two) heavy.
Sources
- NIST SI conversion factors (checked October 4, 2026)
- NFPA 70 (NEC) — Chapter 9 Table 8 conductor properties (circular mils and 75 °C DC resistance)
- NEC Table 310.16 copper 75 °C ampacity and 240.4(D) small-conductor OCPD caps (15 / 20 / 30 A)
- IAEI Magazine — Voltage Drop Formulas (March 2017): copper K = 12.9 at 75 °C from Table 8
Related calculators
Some product links on this site may be affiliate links; we may earn a commission at no extra cost to you. Read the Affiliate Disclosure.